Universal conductor terminal 1.5 - 16 mm²

Universal conductor 1,5-16mm2

189,60  / sales pack Sales pack incl. 100 KPLReference price 1,9 / 100KPL

In stock (can be backordered)

Product number: 01289WProduct order number: 01289Manufacturer's product number: 01289Product commodity code: 85369010

The Wöhner 01289 is a universal conductor terminal designed for flat busbars with a thickness of 10 mm. It accepts copper conductors in the range of 1.5 to 16 mm² (AWG 16–6), making it flexible for different wiring needs. The terminal is rated for 65 A and up to 800 V AC, ensuring reliable performance in demanding environments. Its screw clamp connection with PZ2 drive guarantees a secure and durable installation. With compact dimensions of 12 × 23 × 25 mm and a weight of 2.3 kg per 100 pieces, it is well-suited for space-saving panel designs.

Weight 0,023 kg
Quantity in the package: 100Unit: KPL

Standards: IEC 61439-1:2020
Standards: IEC 60999-1:1999
Standards: IEC 60999-2:2003
Rated current (IEC): 65 A
Rated voltage (IEC) AC: 800 V
Rated peak withstand current Ipk max.: 30.6 kA
Power dissipation at 80% load (typical): 0.0 W
Power dissipation at full load: 0.0 W
Max. permitted voltage (IEC) AC: 1000 V
Max. permitted voltage (IEC) DC: 1500 V
Current capacity (IEC) max.: 180 A
Standards (UL): UL 508
Suitable for: field-installed conductors
Rated current (UL): 65 A
Rated voltage (UL) AC: 600 V
Rated frequency (UL): 50 / 60 Hz
For wires UL: Cu 75°C
W x H x D: 12 x 23 x 25
Weight: 2.3 kg/100
For busbars: flat busbars 10 mm
Terminal points: screw clamp connection
Screw drive: PZ2
Min. cross-section: 1.5 mm²
Max. cross-section: 16 mm²
re: 1.5 - 16 mm²
rm: 1.5 - 16 mm²
f: 1.5 - 16 mm²
f + AE: 1.5 - 16 mm² (may not fit with max. cross-section)
Md min.: 3.2 Nm
Md max.: 4.8 Nm
Note: Not suitable for aluminium cables!
Terminal space: 7 x 7
Laminated Cu width: 5 - 7 mm
Laminated Cu thickness: 3 - 7 mm
Number of laminated Cu: 1
Min. cross-section (UL): AWG 16
Max. cross-section (UL): AWG 6
For wires UL: Cu 75°C
Note: Supplementary values verified under specific test conditions; consult Wöhner before panel design.